AMB-6D Megohmmeter/Insulation Tester |
|
|
|
| |
The AMB-6D's full suite of features translate
into robust functionality, durable and dependable Benefits:
- Ideal for checking motor windings and cable insulation.
- Fast and easy to use.
- Warns against hazardous energized systems.
- Designed for use in remote locations.
- Software provided for printing reports.
- All accessories and software are included with product.
|

|
Features
- Tests insulation of wires, cables, transformers and electrical
motors.
- Comes as a complete kit including test leads and PC software.
- Selectable test voltages up to 1000V.
- Programmable timer to perform the Dielectric Absorption Ratio
Test.
- Sensitive Ohmmeter for checking resistance of motor windings.
- Selectable polarization of ohmmeter for checking grounding
continuity.
- Automatic voltmeter warns against hazardous energized systems.
- Fast and easy to use, rugged durable design.
- Internal memory to store measurements for future reference.
- Data download to PC.
- Battery operated.
 |
|
| Specifications |
| |
| Continuity: |
|
Test Mode |
Measuring Range |
Resolution |
Accuracy |
|
AUTO, R+, R |
0.01Ω to 19.99Ω |
0.01Ω |
±(2%
of Rdg + 2 digits) |
| 20.0Ω to 99.9Ω |
0.1Ω |
|
R +Timer
R -Timer |
0.01Ω to 9.99Ω |
0.01Ω |
±(2% of Rdg + 2
digits) |
|
| |
| Test Current: |
>200mA DC up to 16Ω (includes
the resistance of the calibration) |
| |
40mA DC from 16Ω to 99.9Ω |
| Test Current Resolution: |
1mA |
| Open Circuit Test Voltage |
9V |
|
| |
| Insulation Resistance: |
|
Test Voltage |
Measuring Range (MΩ) |
Resolution |
Accuracy |
| 50V |
0.01MΩ to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2
digits) |
| 20.0MΩ to 49.9MΩ |
0.1Ω |
±(5% of Rdg + 2
digits) |
| 50.0MΩ to 99.9MΩ |
0.1Ω |
±(5% of Rdg + 2
digits) |
| 100V |
0.01MΩ to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2
digits) |
| 20.0MΩ to 99.9MΩ |
0.1Ω |
±(2% of Rdg + 2
digits) |
| 100.0MΩ to 199.9MΩ |
0.1Ω |
±(5% of Rdg + 2
digits) |
| 250V |
0.01MΩ to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2
digits) |
| 20.0MΩ to 199.9MΩ |
0.1Ω |
±(2% of Rdg + 2
digits) |
| 200MΩ to 249MΩ |
1Ω |
±(2% of Rdg + 2
digits) |
| 250MΩ to 499MΩ |
1Ω |
±(5% of Rdg + 2
digits) |
| 500V |
0.01MΩ to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2
digits) |
| 20.0MΩ to 199.9MΩ |
0.1Ω |
±(2% of Rdg + 2
digits) |
| 200MΩ to 499MΩ |
1Ω |
±(2% of Rdg + 2
digits) |
| 500MΩ to 999MΩ |
1Ω |
±(5% of Rdg + 2
digits) |
| 1000V |
0.01MΩ to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2
digits) |
| 20.0MΩ to 199.9MΩ |
0.1Ω |
±(2% of Rdg + 2
digits) |
| 200MΩ to 999MΩ |
1Ω |
±(2% of Rdg + 2
digits) |
| 1000MΩ to 1999MΩ |
1Ω |
±(5% of Rdg + 2
digits) |
|
| |
| |
| Automatic selection of the measuring range |
| Open Circuit Voltage: |
1.1 x Rated voltage test |
| Short Circuit Current: |
<3.0mA to 500V |
| |
<2.0mA to 50V, 100V, 250V, 1000V |
| Rated Measurement Current: |
2.17mA to 500V/230kΩ |
| |
1.0mA to 1000V/1MΩ |
|
| If the instrument measures a voltage higher than 30V, the instrument
will not take a measurement. |
| |
| |
General Specifications (23°C
±5°C <70% R.H.)
|
| Display: |
Custom LCD |
| Memory: |
350 tests |
| Interface: |
Optical RS-232 to print or download the tests |
| |
|
| Environmental: |
|
| Operating Temperature: |
-10°C to 50°C
(14°F to 140°F)
<80% R.H. |
| Storage Temperature: |
-20°C to 60°C
(68°F to 140°F)
<70% R.H. |
| |
|
| EMC: |
|
| Radiated Emissions: |
EN 55011 |
| Immunity: |
EN 50140, EN 61000 |
| Electrostatic Discharge: |
EN 61000-4-2 |
| R.F. Field: |
EN 50140 |
| Fast Transient: |
EN 61000-4-4 |
| |
|
| Safety: |
|
| Insulation: |
Class 2, double insulated |
| Over-voltage Category: |
CAT III, 300V |
| |
|
| Mechanical: |
|
| Dimensions: |
222mm (L) x 162mm (W) x 57mm (D) |
| |
8.8" (L) x 6.4" (W) x 2.25" (D) |
| Weight: |
1000gms (2.2lb) |
| |
|
| Battery Supply: |
6ea. 1.5V type 'AA' batteries |
| Automatic Turn Off: |
Turns off after 5 minutes without use |
|
| |
|
Included Accessories |
|
Test Leads (complete set with
cables, alligator clip and probes), Serial cable,
software, and user's manual. |
|
| |
| |