DGC-1000A Ground Resistance Tester |
|
|
|
| |
|
User-friendly and accurate. Think safety and
Amprobe's DGC-1000A Ground Resistance tester second. Use the
on-board memory and data logging to make your work more efficient. |
|
 |
Features
- Accurate ground resistance measurement from 0.025Ω
to 1500Ω.
- True RMS current measurement including
leakage current.
- Accurate readings regardless of power
quality in less than 10 seconds.
- Continuity beep if the resistance is
lower than 40.00Ω.
- Simple and easy to use, no test leads or
auxiliary electrodes necessary.
- Data logging capability - 116 records.
- Individual data point recording.
- User selectable High and Low Ohm audible
alarms.
- Auto power Off (can be disabled).
- Low battery indicator.
- Large LCD display.
- CAT III 300V, CAT II 600V.
|
|
| |
| Specifications |
| |
| Ground Resistance (Auto Range): |
| Range |
Resolution |
Accuracy |
|
0.025Ω to 0.250Ω |
0.002Ω |
±1.5% ±0.05Ω |
|
0.250Ω to 1.000Ω |
0.02Ω |
±1.5% ±0.05Ω |
|
1.001Ω to 9.999Ω |
0.02Ω |
±1.5% ±0.1Ω |
|
10.00Ω to 50.00Ω |
0.04Ω |
±2.0% ±0.3Ω |
|
10.01Ω to 99.99Ω |
0.04Ω |
±2.0% ±0.5Ω |
|
100.0Ω to 200.0Ω |
0.4Ω |
±3.0% ±1.0Ω |
|
200.1Ω to 400.0Ω |
2Ω |
±5.0% ±5Ω |
|
400.0Ω to 600.0Ω |
5Ω |
±10% ±10Ω |
|
600.1Ω to 1500Ω |
20Ω |
±20% |
|
| |
| High and Low Alarm: |
| Range |
Range |
Resolution |
|
High Alarm |
0Ω to 1510Ω |
1Ω |
|
Low Alarm |
0Ω to 1510Ω |
1Ω |
|
| |
| Ground Leakage Current (Auto Range, 50/60Hz, True-rms,
Crest Factor <3.0) |
| Range |
Resolution |
Accuracy |
|
0.200mA to 1.000mA |
0.001mA |
±2.0% ±0.05mA |
|
1.00mA to 10.00mA |
0.01mA |
±2.0% ±0.03mA |
|
10.0mA to 100.0mA |
0.1mA |
±2.0% ±0.3mA |
|
100mA to 1000mA |
1mA |
±2.0% ±3mA |
|
0.200A to 4.000A |
0.001A |
±2.0% ±0.03mA |
|
4.00A to 30.00A |
0.01A |
±3.0% ±0.03mA |
|
| |
| Accuracy of Resistance Calibration Plate: ±0.5% |
| Data Logging Capacity: 116 Records |
| Data Logging Interval: 1 to 255 seconds |
| |
| General Specifications |
| |
|
Conductor Size |
23mm (0.9") approx. |
| Display |
4-digits (9999-counts) LCD |
| Sampling Time |
0.5 seconds |
| Range Selection |
Auto |
| Overload Indication |
"OL" |
| Low Battery Indication |
Yes |
| Power Supply |
9 volt IEC 6 LR61 (Alkaline) battery |
| Battery Life |
3000 measurements |
| Operating Temperature |
0°C to 50°C <85%
R.H. (non-condensing) |
| Storage Temperature |
0°C to 60°C <75%
R.H. (non-condensing) |
| Dimensions |
257mm (L) x 100mm (W) x 47mm (D) |
| Weight |
640gms |
| |
|
|
|
Included Accessories |
|
Resistance Calibration Plate,
9V battery, User's manual. |
|
| |
| |