| Voltage
Input Range |
85V to 265V rms,
50/60Hz, 60VA |
| Battery
Life |
6 hours continuous
testing at 5kV |
| Test
Voltages |
250V, 500V, 1000V,
2500V, 5000V |
Accuracy
(23°C, 5kV)
|
±5%
@ 1 TΩ
±20% @ 10 TΩ |
| Guard |
2% error guarding 500kΩ
leakage with 100MΩ load |
| Display
Range |
Digital display
(3-digits) 10kΩ to 15 TΩ
Analog display 100 kΩ to 1 TΩ |
| Short
Circuit/Charge Current |
3mA @ 5 kV |
| Capacitor
Charge Time |
<3 seconds per
µF at 3mA to 5000V |
| Capacitor
Discharge Time |
<120ms per
µF to discharge from 5000V to 50V |
|
Capacitance Measurement (above 500V) |
10nF to 50
µF (depending on test voltage) |
|
Capacitance Measurement Accuracy |
±5%
±5nF (23°C) |
| Voltage
Output Accuracy (0°C to 30°C) |
+4%, -0%
±10V of nominal test voltage at 1 GΩ
load |
| Current
Measurement Range |
0.01 nA to 5mA |
| Current
Measurement Accuracy (23°C) |
±5%
±0.2 nA at all voltages |
|
Interference Rejection |
1 mA rms per 250V test
voltage up to a maximum of 2mA |
| Timer
Range |
Counts up to 99 minutes
from start of test |
| Test
Regimes |
Auto IR |
| Lead Set |
3 leads with compact
clamp, flexible silicon insulated |
| Operating
Temperature |
-10°C
to 50°C |
| Storage
Temperature |
-25°C
to 65°C |
| Ingress
Protection (lid closed) |
IP65 |
| Humidity |
90% R.H. non-condensing
at 40°C |
| Safety |
Meets the requirements
of EN61010-1-2001 CAT III 300V |
| EMC |
Meets the requirements
of EN61326-1:1998 for use in heavy |
| |
industrial areas |
|
Dimensions |
305mm (D) x 194mm (H) x
360mm (W) |
| |
12" (D) x 7.6" (H) x
14.2" (W) |
| Weight |
6.75 kg (15 lb) approx. |