Leda Electronics Logo. Western  Australia's largest distributor of Test Instruments Leda Electronics Showing The Way

 
Megger/Avo > Insulation/Resistance Testers >  Model S1-552

Megger logo AVO logo

Megger Insulation/Resistance Tester Header  

 
 

This new 5kV insulation resistance tester from Megger is designed specifically to assist you with the testing and maintenance of high voltage electrical equipment.

The case is incredibly rugged and easy to carry, being made of tough polypropylene and achieving an ingress protection rating of IP54. In addition, the model number is marked on both the top and side of the case for ease of identification in stores or vehicles.
 

AVO/Megger S1-522 5kV Insulation Tester Megger S1-522
High current insulation resistance tester 5kV

Megger S1-522  5kV Insulation Tester Features

bullet High output current 5mA for fast charging of capacitive loads.
bullet Testing up to 5kV.
bullet Mains or battery powered.
bullet Digital/Analog backlit display.
bullet Variable test voltage from 50V to 5,000V.
bullet Automatic IR, PI, DAR, SV and DD tests.
bullet Measures to 15 TΩ.
bullet RS-232 and USB download of results.
 

Megger S1-522  5kV Insulation Tester Specifications
 

Voltage Input Range 85V to 265V rms, 50/60Hz, 60VA
Battery Life 6 hours continuous testing at 5kV
Test Voltages 50V to 1kV in 10V steps. 1kV to 5kV in 25V steps
Accuracy (23°C, 5kV)
 
±5% to 1 TΩ
±
20% to 10 TΩ
Guard 2% error guarding 500kΩ leakage with 100MΩ load
Display Range Digital display (3-digits) 10kΩ to 15 TΩ
Analog display 100 kΩ to 1
TΩ
Short Circuit/Charge Current 5mA @ 5 kV
Capacitor Charge Time <1.5 seconds per µF at 5mA to 5000V
Capacitor Discharge Time <120ms per µF to discharge from 5000V to 50V
Capacitance Measurement (above 500V) 10nF to 50 µF (depending on measurement voltage)
Capacitance Measurement Accuracy ±5% ±5nF (23°C)
Voltage Output Accuracy (0°C to 30°C) +4%, -0% ±10V of nominal test voltage at 1 GΩ load
Current Measurement Range 0.01 nA to 5mA
Current Measurement Accuracy (23°C) ±5% ±0.2 nA at all voltages
Interference Rejection 1 mA rms per 250V test voltage up to a maximum of 2mA
Timer Range Up to 99 minutes and 59 seconds from start of test
15 second minimum setting for test voltage 1000V
30 second minimum setting for test voltage <1000V
Memory Capacity 32kB
Test Regimes Auto IR, PI, DAR, SV,DD
Interface RS-232 and USB
Data Store Voltage, test time, leakage current, PI, DAR, DD, capacitance and time constant
Real Time Output Serial, once per second of test voltage, current and resistance
Operating Temperature -10°C to 50°C
Storage Temperature -25°C to 65°C
Ingress Protection (lid closed) IP65
Humidity 90% R.H. non-condensing at 40°C
Safety Meets the requirements of EN61010-1-2001 CAT III 300V
EMC Meets the requirements of EN61326-1:1998 for use in heavy industrial areas
Dimensions 305mm (D) x 194mm (H) x 360mm (W)
  12.7" (D) x 7.6" (H) x 14.2" (W)
Weight 7.1 kg (16 lb) approx.

 

 

Home | Amprobe | CIE | EuroSMC | Fluke | Kyoritsu-Kew |Megger | Reed | Yokogawa | Site Map | Search

Leda Electronics Pty. Ltd.
A.C.N. 078 681 562           A.B.N. 83 078 681 562
P.O. Box 1733 Malaga, LPO WA 6944
                                                      Unit 5, 31 Century Road, Malaga, Western Australia 6090                                                            
Phone: 61 8 9248 6688    Fax: 61 8 9248 6227

information@ledaelectronics.com.au

          Copyright © 2000 - 2011                                                                Last Modified: Thursday, 15 September 2011