Fluke Power Quality Recorders

   
Model 1750 Three-Phase Power Quality Recorder - Specifications  
 
 
Power Quality Measurement Standards
 

Conformance:
 

IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on measurement function, IEEE519, IEEE1159, IEEE1459

Clock/calendar:

Leap years, 24-hour clock

Real-time clock accuracy:

not more than ±1 sec/day

Internal memory capacity for data:

at least 1 GB

Maximum recording period:

at least 31 days

Measurement time control:

automatic

Maximum number of events

limited only by the size of the internal memory

Power requirements:

100V to 240V rms ±10%, 47-63Hz, 40W

Operating time during interruptions (internal UPS operation):

5 minutes per interruption, 60 minutes total operating time without recharging

Dimensions:

215mm x 310mm x 35mm  (8.5" x 12.2" x 3.5")

weight:

6.3kg (14lb)

 
 
Input Specifications
 

Measurement types:


 

One Phase plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye.

Voltage Input channels:

4 AC/DC 

Current Input channels:

5 channels

Voltage channels:
 

Input resistance: 2MΩ
Input capacitance: <20pF

Current input characteristics:
 

2V rms= full scale, 1MΩ input impedance for ferro CT's, low impedance for Flexi-CT's

Measuring method:

 

Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency references used during voltage drops.

 
 
Synchronization and Sampling
 

PLL synchronization source:


 

The PLL synchronizes to the A-N voltage for Wye power types, and to the A-B voltage for Delta power types. All listed power types can be characterized as either Wye or Delta.

PLL lock range :

42.5 to 69Hz

Sampling frequency:

 

Voltage and current: 2.56 samples/cycle inter-harmonics per IEC61000-4-7: 2 560points/10 cycles (50Hz), 3072 points/12 cycles (60Hz) Transient Voltage: 5MHz

A/D resolution:
 

Voltage and current: 24 bits
Transient voltage: 14 bits

 
 
Voltage and Current Measurements
 

AC voltage range:

1000V rms ±10% over range

DC voltage range:

±1000V rms +10% over range

Voltage crest factor:

3 or less

Current measurement range:

Depends on current probe used

Current crest factor:

4 or less

 
 
RMS Voltage Measurement
 

Measurement type:

 

True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60Hz respectively, as required by IEC 61000-4-30.

Measurement uncertainty:
 

AC: ±0.2% of reading ±0.1% of full scale, above 50V rms.
DC: ±0.5% of reading ±0.2% of full scale, above 50V dc.

 
 
RMS Current Measurement
 

Measurement type:

 

True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60Hz respectively, as required by standards.

 
 
Transient Voltage (impulse)
 

Measurement type:

Waveshape sampling

Full scale:

8000 Volts peak

Sample resolution:

200nS

Measurement uncertainty:
 

±5% of reading ±20 V (test parameters: 1000 V DC,
1000V rms, 100 kHz)

 
 
Voltage Swell (rms swell)
 

Measurement type:

 

True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines).

Displayed data:

Amplitude and duration of swell

Measurement:

Same as rms voltage

 
 
Voltage Dip (rms sag)
 

Measurement type:

 

True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines).

Displayed data:

Amplitude and duration of dip or interruption

Measurement:

Same as rms voltage

 
 
Voltage Dropout (interruption)
 

Measurement type:

Same as voltage dip

 
 
LAN Interface
 

Connector:

RJ-45

Speed and type:

10/100 Base-T, auto MDIX

Communications protocol:

TCP/IP over Ethernet

 
 
Wireless Controller Interface
 

Connection:

wireless (2.4 GHz radio)

Speed:

up to 700 kbit/second

Communication protocol:

Bluetooth SPP

 
 
Power Measurement
 

Measurement type:

 

True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60Hz respectively, as required by standards.

 
 
Frequency Measurement
 

Measurement range:

42.5 to 69 Hz

Measurement source:

Same as PLL synchronization source

Measurement accuracy:

±10MHz (10 to 110% of range, with sine wave).

 
 
Power Factor
 

Measurement range:

0.000 to 1.000

Measurement accuracy:
 

±1 digit from the calculation of each measured value (±3 digits for total)

 
 
Displacement Power Factor
 

Measurement method:
 

Calculated from the phase difference between voltage fundamental and current fundamental

Measurement range:

-1000 (leading) to +1000 (lagging)

Measurement accuracy:

±0.5% of reading ±2% of full scale ±1 digit

 
 
Voltage Unbalance and Phase Sequence
 

Measurement method:
 

Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30

 
 
Harmonic Voltage and Current
 

Analysis window:

Rectangular

Analysis order:

1st to 50th order

Measurement accuracy:

Voltage/Current 1st to 0th orders: ±0.5% of reading ±0.2% of full scale, 2nd 1st to 50th orders: ±1% of reading ±0.3% of full scale (current sensor accuracy must be included for current and power)

Measurement method:

IEC 61000-4-7

   

Inter-harmonic Voltage and Current (intermediate harmonics)

Analysis window:

Rectangular

Analysis orders:

1.5 to 49.5th order

Measurement method:

IEC 61000-4-7

 
 
Environmental Specifications
 

Operating environment:

Indoors or in covered area outdoors, up to 2000m altitude

Storage temperature:

-20°C to 50°C

Operating temperature

0°C to 40°C

Humidity:

80% RH maximum non-condensing

 
 
Electrical Safety
 

EMC:

 

EN 61326-1: 1997+A1: 1998 Class A
EN 61000-3-2: 1995+A2: 1998
EN 61000-3-3: 1995

Safety:


 

EN 61010-1-2nd Edition: 2000
Voltage input unit: Contamination Level 2, Overvoltage Category 1000V CAT III, 600V CAT IV (anticipated overvoltage: 8000V)

 
 
Maximum Rated Working Voltage
 

Voltage terminals:

1100 volts rms

Voltage durability:

5550 Vrms AC for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60Hz, 1mA sense current).

Enclosure protection:

IP30 (per EN60529

 

Home | Amprobe | CIE | EuroSMC | Fluke | Kyoritsu-Kew |Megger | Reed | Yokogawa | Site Map | Search

Leda Electronics Pty. Ltd.
A.C.N. 078 681 562           A.B.N. 83 078 681 562
P.O. Box 1733 Malaga, LPO WA 6944
                                                      Unit 5, 31 Century Road, Malaga, Western Australia 6090                                                            
Phone: 61 8 9248 6688    Fax: 61 8 9248 6227

information@ledaelectronics.com.au

          Copyright © 2000 - 2011                                                                Last Modified: Thursday, 15 September 2011