Conformance: |
IEC 61999-1-4
Class 1, IEC 61000-4-30 Class A or B depending on measurement
function, IEEE519, IEEE1159, IEEE1459 |
|
Clock/calendar: |
Leap years,
24-hour clock |
|
Real-time
clock accuracy: |
not more than ±1
sec/day |
|
Internal
memory capacity for data: |
at least 1 GB |
|
Maximum
recording period: |
at least 31 days |
|
Measurement
time control: |
automatic |
|
Maximum
number of events |
limited only by
the size of the internal memory |
|
Power
requirements: |
100V to 240V rms
±10%, 47-63Hz, 40W |
|
Operating
time during interruptions (internal UPS operation): |
5 minutes per
interruption, 60 minutes total operating time without recharging |
|
Dimensions: |
215mm x 310mm x
35mm (8.5" x 12.2" x 3.5") |
|
weight: |
6.3kg (14lb) |
|
| |
| |
 |
| |
|
Measurement
types:
|
One Phase plus Neutral, One Phase IT No Neutral, One Phase Split
Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three
Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2
Element Wye. |
|
Voltage
Input channels: |
4 AC/DC
|
|
Current
Input channels: |
5 channels |
|
Voltage
channels: |
Input
resistance: 2MΩ Input capacitance: <20pF |
|
Current
input characteristics: |
2V rms= full
scale, 1MΩ input impedance for ferro CT's,
low impedance for Flexi-CT's |
|
Measuring
method:
|
Simultaneous digital sampling of voltage and current. Digital PLL
synchronized sampling, internal frequency references used during
voltage drops. |
|
| |
| |
 |
| |
|
PLL
synchronization source:
|
The PLL
synchronizes to the A-N voltage for Wye power types, and to the
A-B voltage for Delta power types. All listed power types can be
characterized as either Wye or Delta. |
|
PLL lock
range : |
42.5 to 69Hz |
|
Sampling
frequency:
|
Voltage and
current: 2.56 samples/cycle inter-harmonics per IEC61000-4-7: 2
560points/10 cycles (50Hz), 3072 points/12 cycles (60Hz) Transient
Voltage: 5MHz |
|
A/D
resolution: |
Voltage and
current: 24 bits Transient voltage: 14 bits |
|
| |
| |
 |
| |
|
AC voltage
range: |
1000V rms ±10%
over range |
|
DC voltage
range: |
±1000V rms +10%
over range |
|
Voltage
crest factor: |
3 or less |
|
Current
measurement range: |
Depends on
current probe used |
|
Current
crest factor: |
4 or less |
|
| |
| |
 |
| |
|
Measurement
type:
|
True rms
calculated continuously: every cycle, every 1/2 cycle, and every
10 or 12 cycles at 50 or 60Hz respectively, as required by IEC
61000-4-30. |
|
Measurement
uncertainty: |
AC: ±0.2% of
reading ±0.1% of full scale, above 50V rms. DC: ±0.5% of reading ±0.2% of full scale, above 50V dc. |
|
| |
| |
 |
| |
|
Measurement type:
|
True rms
calculated continuously: every cycle, every 1/2 cycle, and every
10 or 12 cycles at 50 or 60Hz respectively, as required by
standards. |
|
| |
| |
 |
| |
|
Measurement
type: |
Waveshape
sampling |
|
Full scale: |
8000 Volts peak |
|
Sample
resolution: |
200nS |
|
Measurement
uncertainty: |
±5% of reading
±20 V (test parameters: 1000 V DC, 1000V rms, 100 kHz) |
|
| |
| |
 |
| |
|
Measurement
type:
|
True rms (one
cycle calculation by overlapping each half cycle - voltage between
lines is measured for 3P3W lines and phase voltage is measured for
3P4W lines). |
|
Displayed
data: |
Amplitude and
duration of swell |
|
Measurement: |
Same as rms
voltage |
|
| |
| |
 |
| |
|
Measurement
type:
|
True rms (one
cycle calculation by overlapping each half cycle - voltage between
lines is measured for 3P3W lines and phase voltage is measured for
3P4W lines). |
|
Displayed
data: |
Amplitude and
duration of dip or interruption |
|
Measurement: |
Same as rms
voltage |
|
| |
| |
 |
| |
|
Measurement
type: |
Same as voltage
dip |
|
| |
| |
 |
| |
|
Connector: |
RJ-45 |
|
Speed and
type: |
10/100 Base-T,
auto MDIX |
|
Communications protocol: |
TCP/IP over
Ethernet |
|
| |
| |
 |
| |
|
Connection: |
wireless (2.4
GHz radio) |
|
Speed: |
up to 700
kbit/second |
|
Communication protocol: |
Bluetooth SPP |
|
| |
| |
 |
| |
|
Measurement
type:
|
True rms
calculated continuously: every cycle, and every 10 or 12 cycles at
50 or 60Hz respectively, as required by standards. |
|
| |
| |
 |
| |
|
Measurement
range: |
42.5 to 69 Hz |
|
Measurement
source: |
Same as PLL
synchronization source |
|
Measurement
accuracy: |
±10MHz (10 to
110% of range, with sine wave). |
|
| |
| |
 |
| |
|
Measurement
range: |
0.000 to 1.000 |
|
Measurement
accuracy: |
±1 digit from
the calculation of each measured value (±3 digits for total) |
|
| |
| |
 |
| |
|
Measurement
method: |
Calculated from
the phase difference between voltage fundamental and current
fundamental |
|
Measurement
range: |
-1000 (leading)
to +1000 (lagging) |
|
Measurement
accuracy: |
±0.5% of reading
±2% of full scale ±1 digit |
|
| |
| |
 |
| |
|
Measurement
method: |
Positive
sequence voltage divided by negative sequence voltage, per IEC
61000-4-30 |
|
| |
| |
 |
| |
|
Analysis
window: |
Rectangular |
|
Analysis
order: |
1st to 50th
order |
|
Measurement
accuracy: |
Voltage/Current
1st to 0th orders: ±0.5% of reading ±0.2% of full scale, 2nd 1st
to 50th orders: ±1% of reading ±0.3% of full scale (current sensor
accuracy must be included for current and power) |
|
Measurement
method: |
IEC 61000-4-7 |
| |
|
|
Inter-harmonic Voltage and
Current (intermediate harmonics) |
|
Analysis
window: |
Rectangular |
|
Analysis
orders: |
1.5 to 49.5th
order |
|
Measurement
method: |
IEC 61000-4-7 |
|
| |
| |
 |
| |
|
Operating
environment: |
Indoors or in
covered area outdoors, up to 2000m altitude |
|
Storage
temperature: |
-20°C
to 50°C |
|
Operating
temperature |
0°C
to 40°C |
|
Humidity: |
80% RH maximum
non-condensing |
|
| |
| |
 |
| |
|
EMC:
|
EN 61326-1:
1997+A1: 1998 Class A EN 61000-3-2: 1995+A2: 1998 EN 61000-3-3: 1995 |
|
Safety:
|
EN 61010-1-2nd Edition: 2000 Voltage input unit: Contamination Level 2, Overvoltage Category
1000V CAT III, 600V CAT IV (anticipated overvoltage: 8000V) |
|
| |
| |
 |
| |
|
Voltage
terminals: |
1100 volts rms |
|
Voltage
durability: |
5550 Vrms AC for 1 minute, between voltage input terminals,
voltage input terminals and current probes, and voltage input
terminals and case (50/60Hz, 1mA sense current). |
|
Enclosure
protection: |
IP30 (per
EN60529 |
|