Leda Electronics Logo. Western  Australia's largest distributor of Test Instruments Leda Electronics Showing The Way

 
 
Fluke Test Instruments Logo

Fluke Clamp Meters

   
330 Series Clamp Meters - Specifications  
 
 
330 Series Clamp Meter Specifications
Voltage DC Range: 0 - 600.0 V
Accuracy: 1% ± 5 counts
Voltage AC Fluke 333/334
Range: 0 - 600.0 V
Accuracy: 1% ± 5 counts (50/60 Hz)
AC Response: Averaging

Fluke 335

Range: 0 - 600.0 V
Accuracy: 1% ± 5 counts (50/60 Hz)
AC Response: True-rms

Fluke 336/337
Range: 0 - 600.0 V
Accuracy: 1% ± 5 counts (20-100 Hz), 6% ± 5 counts (100-400 Hz)
AC Response: True-rms
Current DC Fluke 336
Range: 0 - 600.0 A
Accuracy: 2% ± 3 counts

Fluke 337
Range: 0 - 999.9 A
Accuracy: 2% ± 3 counts
Current AC Fluke 333/334
Range: 0 - 400.0 A
Accuracy: 2% ± 5 counts (50/60 Hz)
AC Response: Averaging

Fluke 335
Range: 0 - 600.0 A
Accuracy: 2% ± 5 counts (50/60 Hz)
Crest Factor(50/60 Hz): 2.4 @ 500A, 2.0 @ 600A, add 2% for CF>2
AC Response: True-rms

Fluke 336
Range: 0 - 600.0 A
Accuracy: 2% ± 5 counts (10-100 Hz), 6% ± 5 counts (100 - 400 Hz)
Crest Factor(50/60 Hz): 3 @ 500A, 2.5 @ 600A, add 2% for CF>2
AC Response: True-rms

Fluke 337
Range: 0 - 999.9 A
Accuracy: 2% ± 5 counts (10-100 Hz), 6% ± 5 counts (100 - 400 Hz)
Crest Factor(50/60 Hz): 3 @ 500A, 2.5 @ 600A, 1.42@1000 A, add 2% for CF>2
AC Response: True-rms
Resistance Fluke 333
Range: 0 - 600.0 W
Accuracy: 1.5% ± 5 counts

Fluke 334/335/336/337
Range: 0 - 600.0 W, 6001 - 6000 W
Accuracy: 1.5% ± 5 counts
Frequency Fluke 337
Range: 5 - 400Hz
Accuracy: 0.5% ± 5 counts
Trigger Level: 10-100 Hz >= 5A, 5-10 Hz, 100-400 Hz >=10A
Inrush Current Fluke 334/335/336/337
Integration Time: 100 ms
Continuity 30 Ω
MIN/MAX Fluke 337 only
 
 
330 Series Clamp Meter Environmental Specifications
Operating Temperature -10°C to +50°C
Storage Temperature -40ºC to +60ºC
Operating Altitude 2,500 meters
Temperature De-rating Add 0.1 x specified accuracy for each ºC above 28ºC or below 18ºC
 
 
330 Series Clamp Meter safety Specifications
Safety Rating IEC 1010-2-032, 600V CAT III
 
 
330 Series Clamp Meter Mechanical and General Specifications
Size Fluke 333/334/335
240 x 80 x 40 mm

Fluke 336/337
250 x 80 x 40 mm
Weight 310 g
Warranty Three years
Battery life Alkaline approximately 150 hours continuous
Automatic low battery indicator
Backlight Fluke 334/335/336/337
Display Hold Yes

 

Home | Amprobe | CIE | EuroSMC | Fluke | Kyoritsu-Kew |Megger | Reed | Yokogawa | Site Map | Search

Leda Electronics Pty. Ltd.
A.C.N. 078 681 562           A.B.N. 83 078 681 562
P.O. Box 1733 Malaga, LPO WA 6944
                                                      Unit 5, 31 Century Road, Malaga, Western Australia 6090                                                            
Phone: 61 8 9248 6688    Fax: 61 8 9248 6227

information@ledaelectronics.com.au

          Copyright © 2000 - 2011                                                                Last Modified: Thursday, 15 September 2011