Current
measurement
dc and ac
10Hz to 100Hz
|
| Range 40A |
Resolution: |
10mA |
| |
Current Accuracy: |
1.5% of reading + 15
digits |
| |
Trigger Level for
Inrush: |
0.50A |
| |
Trigger Level for Hz Filter OFF: |
2.50A |
| |
Trigger Level for Hz Filter ON: |
0.50A |
|
Range 400A |
Resolution: |
100mA |
| |
Current Accuracy: |
1.5% of reading + 5
digits |
| |
Trigger Level for
Inrush: |
5.0A |
| |
Trigger Level for
Hz Filter OFF: |
2.5A |
| |
Trigger Level for Hz Filter ON: |
2.5A |
|
Range 2000A; |
Resolution: |
1A |
| 1400A ac rms |
Current Accuracy: |
1.5% of reading + 5
digits |
| |
Trigger Level for
Inrush: |
5A |
| |
Trigger Level for
Hz Filter OFF: |
8A |
| |
Trigger Level for
Hz Filter ON: |
8A |
|
Crest Factor
50/60Hz
|
| Range 40A |
Crest Factor*: |
2 @ 33A, 2.4 @ 27A |
| Range 400A |
Crest Factor*: |
2 @ 330A, 2.4 @ 270A |
| Range 2000A; |
Crest Factor*: |
2 @ 1000A, 2.4 @
833A |
| 1400A ac rms |
Note*: Add 2% to error spec for CF
>2 |
|
Current
Measurement
ac 100.1Hz to 1kHz
|
| Range 40A |
Resolution: |
10mA |
| |
Current Accuracy
>10A: |
3.5% of reading + 15
digits |
| |
Trigger Level for
Inrush: |
0.50A |
| |
Trigger Level for Hz Filter OFF: |
2.50A |
| |
Trigger Level for Hz Filter ON: |
0.50A |
|
Range 400A |
Resolution: |
100mA |
| |
Current Accuracy
>10A: |
3.5% of reading + 5
digits |
| |
Trigger Level for
Inrush: |
5.0A |
| |
Trigger Level for
Hz Filter OFF: |
2.5A |
| |
Trigger Level for Hz Filter ON: |
2.5A |
|
Range 2000A; |
Resolution: |
1A |
| 1400A ac rms |
Current Accuracy
>10A: |
3.5% of reading + 5
digits |
| |
Trigger Level for
Inrush: |
5A |
| |
Trigger Level for
Hz Filter OFF: |
8A |
| |
Trigger Level for
Hz Filter ON: |
8A |
|
Voltage
measurement (355 only) dc and ac 10Hz to 100Hz (600V and 1000V
ranges have 10% over range to 660V and 1100V respectively)
|
| Range 4V |
Resolution: |
10mV |
| |
Accuracy: |
1.0% of reading + 10
digits |
| |
Trigger Level for Hz Filter OFF: |
0.050V |
| |
Trigger Level for Hz Filter ON: |
0.050V |
|
Range 40V |
Resolution: |
10mV |
| |
Accuracy: |
1.0% of reading + 5
digits |
| |
Trigger Level for
Hz Filter OFF: |
0.25V |
| |
Trigger Level for Hz Filter ON: |
0.25V |
|
Range 400V |
Resolution: |
100mV |
| |
Accuracy: |
1.0% of reading + 5
digits |
| |
Trigger Level for Hz Filter OFF: |
6V |
| |
Trigger Level for Hz Filter ON: |
6V |
|
Range 600V |
Resolution: |
1V |
|
ac rms |
Accuracy: |
1.0% of reading + 5
digits |
| |
Trigger Level for Hz Filter OFF: |
6V |
| |
Trigger Level for Hz Filter ON: |
6V |
|
Range 1000V dc |
Resolution: |
1V |
| |
Accuracy: |
1.0% of reading + 5
digits |
|
Voltage
measurement (355 only) ac 100.1Hz to 1kHz (600V and 1000V ranges
have 10% over range to 660V and 1100V respectively)
|
| Range 4V |
Resolution: |
1mV |
| |
Accuracy: |
3.0% of reading + 10
digits |
| |
Trigger Level for Hz Filter OFF: |
0.050V |
| |
Trigger Level for Hz Filter ON: |
0.050V |
|
Range 40V |
Resolution: |
10mV |
| |
Accuracy: |
3.0% of reading + 5
digits |
| |
Trigger Level for
Hz Filter OFF: |
0.25V |
| |
Trigger Level for Hz Filter ON: |
0.25V |
|
Range 400V |
Resolution: |
100mV |
| |
Accuracy: |
3.0% of reading + 5
digits |
| |
Trigger Level for Hz Filter OFF: |
6V |
| |
Trigger Level for Hz Filter ON: |
6V |
|
Range 600V |
Resolution: |
1V |
|
ac rms |
Accuracy: |
3.0% of reading + 5
digits |
| |
Trigger Level for Hz Filter OFF: |
6V |
| |
Trigger Level for Hz Filter ON: |
6V |
|
Ohms
measurement (355 only)
|
|
Range 400Ω |
Resolution: |
0.1Ω |
| |
Accuracy: |
1.5% of reading + 5 digits |
|
Range 4kΩ |
Resolution: |
1Ω |
| |
Accuracy: |
1.5% of reading + 5 digits |
| Range 40kΩ |
Resolution: |
10Ω |
| |
Accuracy: |
1.5% of reading + 5 digits |
|
Range 400kΩ |
Resolution: |
100Ω |
| |
Accuracy: |
1.5% of reading + 5
digits |
|
Continuity
beeper
(355 only) |
On at
≤30Ω
Off at ≥100Ω |
Frequency
measurement
|
|
Measurement |
Range: |
5.0Hz to 1kHz |
| |
Resolution: |
0.1Hz (15Hz to 399.9Hz); 1Hz (400Hz
to 1kHz) |
| |
Accuracy: |
0.2% + 2 counts (5.0Hz to 100Hz) |
| |
Accuracy: |
0.5% + 5 counts (100.1Hz to 1kHz) |
| |
Trigger level: |
Refer to current and voltage tables |
|