Leda Electronics Logo. Western  Australia's largest distributor of Test Instruments Leda Electronics Showing The Way
 
 
Fluke Test Instruments Logo

Fluke Accessories

 
MBX Clamp 20A/200A Current Clamp  
 
Fluke Model MBX Clamp 20A/200A Current Clamps. Four precision dual range current clamps (20 amp and 200 amp) for secondary current transformer applications.

Four precision dual range current clamps (20 amp and 200 amp) for secondary current transformer applications.

Expand the capabilities of the Fluke 1735 and 1740 Series Loggers with these dual-range current clamps. The accessory includes four precision clamps that are automatically detected and scaled by the instrument when attached.

 

 
Model MBX 20A/200A Current Clamp Specifications

Electrical Characteristics

Nominal current in:

Overload:

Conductor position influence:

Error due to adjacent conductor:

Phase shift at 2kHz at 200A:

Frequency range:

Temperature coefficient:

Working voltage (see safety section):

Order reference:

 

 

200Amps AC rms

up to 300Amps rms

<0.5% of range at 50/60 Hz

less than or equal to 15mA/A at 50Hz

< ±1 degree

40 Hz to 10 kHz (-3 dB)

0.015% of range /°C

600 Volts AC rms or DC

single-phase: EP0443A
three-phase: EP0455A
three-phase+N: EP0456A

Accuracy

Primary current 0.5A to 10A:
 

Primary current 10A to 50A:
 

Primary current 50A to 100A:
 

Primary current 100A to 200A:
 

 

Operating error in % of reading: ±2.5%
Phase Shift: not specified

Operating error in % of reading: ±1.5%
Phase Shift: <2°

Operating error in % of reading: ±0.5%
Phase Shift: <0.5°

Operating error in % of reading: ±0.5%
Phase Shift: <1°

General Characteristics

Maximum conductor size:

Cable length:

Operating temperature range:

Storage temperature range:

Operating humidity:

Weight per clamp:

 

15mm diameter, bus bar 15mm x 17mm

2 meters

-10°C to +55°C

-20°C to +70°C

15% to 85% R.H. (non condensing)

175 gms

Reference Conditions

Environmental temperature range:

Humidity:

Current:
 

Load impedance for voltage output:

 

+18°C to +26°C

20% to 75% R.H.

sinusoidal waveform, 48 to 65Hz, distortion factor: <1%, no DC component

greater than or equal to 1m ohm, <100pF

Safety Standards

IEC/EN61010-1: 2001
IEC/EN61010-2-032
IEC/EN61010-2-031

Safety

600V CAT III, pollution degree 2
The application of the clamps on uninsulated conductors is limited to 600V AC rms or DC to ground and frequencies below 1kHz

EMC Standards

EN61326-1: 1997/A1: 1998

Dimensions

102mm x 42.5mm x 23.5mm

 

Home | Amprobe | CIE | Fluke | Kyoritsu-Kew |Megger | Reed | Yokogawa | Site Map | Search

Leda Electronics Pty. Ltd.
A.C.N. 078 681 562           A.B.N. 83 078 681 562
                                                      14 Wright Street Kewdale, Western Australia 6105                                                            
Phone: 61 8 9472 4444          Fax: 61 8 9472 4644

information@ledaelectronics.com.au

          Copyright © 2000 - 2007                                                                          Last Modified: Friday, 09 July 2010