Parameter |
Specification |
|
Method of detection |
Mean Value |
|
Display |
LCD (Digital display:1999 counts) |
|
Response Time |
Approx. 2 seconds |
|
Range Switching |
Manual range |
|
Data Hold |
On all ranges |
|
Peak Hold |
N/A |
|
Ambient Temperature and Humidity |
0 to 40°C
85% RH or less (no condensation) |
|
Temperature Coefficient |
N/A |
|
Influence of External Magnetic Field |
10mA or less in proximity to a 14.4mm-dia
conductor carrying 100Amps. |
|
Influence of Conductor Position |
Within 5dgt for 0 to 50A, or 2% for 50A to 200A
(10mm-dia conductor at inside the jaw) |
|
Influence of residual current |
10mA or less in proximity to a 10mm-dia
conductor carrying 50Amps. |
|
Safety Standard |
EN61010-1, EN61010-2-032 (CAT III 300V) |
|
Circuit Voltage |
300Vrms or less |
|
Withstanding Voltage |
3.7kV AC for one minute |
|
Power Supply |
LR-44 x 2 (3V) or SR-44 x 2 |
|
Battery Life |
Approx. 15 hours (continuous) |
|
Consumed Current |
Approx. 5mA |
|
Auto Power Off |
Approx. 10 minutes |
|
Diameter of Measurable Conductor |
24mm maximum |
|
Dimensions |
Approx. 60mm (W) x 149mm (H) x 26mm (D) |
|
Weight |
Approx. 120g |
|
Accessories |
User's manual (IM CL320), Batteries & Carrying
Case (93033) |