Leda Electronics Logo. Western  Australia's largest distributor of Test Instruments Leda Electronics Showing The Way

 
Portable and Hand-Held Instruments > Model CL340
Yokogawa Test and Measurement Logo

Portable and Hand-Held Instruments Including: ● Calibrators ● DMMs ● Clamp-On Testers ● Portable Data Loggers ● Insulation Testers ● Thermometers ● Portable Analog Meters ● Light Meters, and ● Precision Measuring Equipment.

Model CL340
Clamp-On Tester for AC Leakage Current Measurements

Yokogawa Model CL340 Clamp Meter for AC Leakage Current Measurements

Yokogawa CL340 Features
 
bullet Mean value display.
bullet Leakage current measurement with current range from 40mA to 400A.
bullet 40mm in diameter of measurable conductor.
bullet Auto power off.
bullet Manual range switching.
bullet Approved for conformity to safety standards EN61010-1, EN61010-2-032 (CAT III 300V)
 
 
Yokogawa Model CL340 Specifications
 

Parameter

Reference

Accuracy

AC Current
 

  Wide (20Hz to 1kHz) 50/60Hz

40mA/400mA

2.5+10 (20 to 1kHz)

1.0+5 (50/60Hz)

400A (0 to 350A)

2.5+10 (40 to 1kHz)

 

400A (350 to 400A)

5.0  (40 to 1kHz)

2.0 (50/60Hz)

 
At 23°C ±5°C, 75% RH or less
Accuracy: ±(% rdg + dgt) = ±(% readout + value of least significant digit)
 
 
Yokogawa Model CL340 General Specifications
 

Parameter

Specification

Method of detection

Mean Value

Display

LCD (Digital display:3999 counts)

Response Time

Approx. 2 seconds

Range Switching

Manual range

Data Hold

On all ranges

Peak Hold

On all ranges

Ambient Temperature and Humidity

0 to 40°C
85% RH or less (no condensation)

Temperature Coefficient

N/A

Influence of External Magnetic Field

10mA or less in proximity to a 15mm-dia conductor carrying 100Amps.

Influence of Conductor Position

40/400mA range: Within 5dgts at every part inside the jaw (400A range).
0 to 250A range: Within  ±0.5% rdg ±5dgt at every part inside the jaw section.

Influence of residual current

12mA or less in proximity to a 10mm-dia conductor carrying 100Amps.

Safety Standard

EN61010-1, EN61010-2-032 (CAT III 300V)

Circuit Voltage

300Vrms or less

Withstanding Voltage

3.7kV AC for one minute

Power Supply

R0-3(UM-4) x 2 or LR03 x 2

Battery Life

Approx. 40 hours (continuous)

Consumed Current

Approx. 13mA

Auto Power Off

Approx. 10 minutes

Diameter of Measurable Conductor

40mm maximum

Dimensions

Approx. 81mm (W) x 185mm (H) x 40mm (D)

Weight

Approx. 270g

Accessories

User's manual (IM CL340), Batteries & Carrying Case (93030)

 

Home | Amprobe | CIE | EuroSMC | Fluke | Kyoritsu-Kew |Megger | Reed | Yokogawa | Site Map | Search

Leda Electronics Pty. Ltd.
A.C.N. 078 681 562           A.B.N. 83 078 681 562
P.O. Box 1733 Malaga, LPO WA 6944
                                                      Unit 5, 31 Century Road, Malaga, Western Australia 6090                                                            
Phone: 61 8 9248 6688    Fax: 61 8 9248 6227

information@ledaelectronics.com.au

          Copyright © 2000 - 2011                                                                Last Modified: Tuesday, 15 November 2011