Measuring
Range |
Earth
Resistance:0-10-100-1,000Ω
(Min
Scale Div 0.1Ω) |
|
|
Earth Voltage:0-30Volts |
|
Scale |
Earth Resistance:3-digit
logarithmic continuous scale on measuring dial. |
|
|
Earth Voltage: Uniform
scale on galvanometer. |
|
Accuracy |
Earth Resistance: |
|
|
±5% of 2Ω(±0.1Ω
or min one div) in range of 0-2Ω |
|
|
±2.5% of 20Ω(±0.5Ω
or min one div) in range of 2-20Ω |
|
|
±2.5% of 200Ω(±5Ω
or min one div) in range of 20-200Ω |
|
|
±5% of 1000Ω(±50Ω
or min one div) in range of 200-1000Ω |
|
|
Earth Voltage:±5% of full
scale |
|
Measuring
Frequency |
500Hz |
|
Ambient
Temperature Influence |
Variation in indication is
within one scale division of corresponding range against a temperature
change of 20±20°C. |
|
Battery Voltage
Influence |
Accuracy is maintained within
specified limit even if voltage decreases to 4 Volts under operating
conditions. |
|
Earth Voltage
Influence |
Variation in indication is
within one scale division of corresponding range for earth voltages up
to 10 Volts at the line frequency. |
|
Power Source |
Four 1.5 Volt batteries (IEC
R20P, ANSI D, Mono 1.5 V or equivalent). |
|
Insulation
Resistance |
More than 20MΩat 500 V DC between terminals and case. |
|
Standard
Accessories |
Supplied With Instrument: |
|
|
Four 1.5 Volt batteries fitted
in Instrument.
Three measuring leads.
Two earth spikes.
One carrying case.
One accessory storage bag. |
|
Optional
Accessory |
B9646CG Auxiliary earthing net
(two sheets per unit). |
|
Size |
190mm (W) x 122mm (H) x 124mm
(D) |
|
Weight |
1.5kg |